SPECIFICATIONS
Rack Size: 2U
Load Capacity: 1000VA / 600W.
Back-Up Run Time: 4 Minute 700W Full Load, 10.4 Minute 350W Half Load
Batteries: 2, user replaceable
Ports: USB
Load Rating: 15 amps @ 120 volts.
Power Requirement (no load): 35 watts (charging) 15 watts (charged)
Surge Let-Through Voltage (6000-volt surge): 0 volts
UL 1449 Adjunct Classification Test Results:
1000 surges, 6000 volts, 3000 amps, B3 pulse;
Measured suppressed voltage: 170 volts; no failures
Federal Guidelines: Grade A, Class 1, Mode 1 (CID A-A-55818)
EMI/RFI Filter, Normal Mode (50-ohm load):
40 dB @ 100 kHz; 50 dB @ 300 kHz;
50 dB @ 3 MHz; 50dB @ 30 MHz
EMI/RFI Filter, Common Mode (50-ohm load):
18 dB @ 300 kHz; 30 dB @ 1 MHz;
50 dB @ 5 MHz; 50 dB @ 20 MHz
Maximum Applied Surge Voltage: 6000 volts*
Maximum Applied Surge Current:
Unlimited, due to current limiting*
Maximum Applied Surge Energy:
Unlimited, due to current limiting*
Endurance (C62.41-1991 Category B3 pulses):
1 kV>500,000; 3 kV>10,000; 6 kV>1000
Dimensions: 3.5" H x 19.0" W x 10.5" D (8.9 x 48.3 x 26.7 cm)
Weight: 32.0 lbs (14.5 kg)
Temperature Range: 5º to 35º C
Humidity Range: 5% to 95% R.H., non-condensing.
Agency Listings: ETL and cETL (UL 1449, 2nd edition;
CSA C22.2 No.8-M1986, R2000)
*1.2 x 50 µs pulse, industry standard combination wave surge, as per IEEE C62.41
Specifications subject to change without notice. SurgeX is a division of Electronic Systems Protection, Inc.
This product, including its components and/or processes carried out thereby, are covered by one or more of the following: U.S. Pat. No. 4,870,534. 4,870,528. 6,728,089. 6,744,613. 7,068,487. Can. Pat. No. 1,333,191. 1,332,439. Other Patents Pending. |
FEATURES
- 2U Rack Mount
- 1000 VA Battery Backup
- Advanced Series Mode® Surge Elimination
- Impedance Tolerant® EMI/RFI Filter
- Automatic Voltage Regulation
- Over/Under Voltage Protection
- SentryPlus™ Power Management and Diagnostic Software
- USB port
- Self-test Circuit and Visual Indicator
- Receptacles: 2 UPS / 4 Surge Elimination
- 10 Year Warranty
- A-1-1 Certified
- RoHS Compliant
- Made in U.S.A.
TECHNICAL DESCRIPTION
The SU-1000Li is a 1000 VA line interactive uninterruptible power supply, surge eliminator, and power conditioner in a magnetically shielded steel enclosure. It operates from 120 volts AC and has a 6-foot, grounded, 3-wire #14 line cord. It has 4 grounded AC receptacles and two of these provide battery back up protection. Overall dimensions are 3.5” H x 19.0” W x 10.5” D. Weight is 32.0 pounds.
The SU-1000Li has a load rating of 15 amps at 120 volts, a self-test circuit with visual indicator, and provides EMI/RFI filtering. It meets Federal Grade A, Class 1, Mode 1 guidelines for power line surge suppressors and withstands at least 1000 occurrences of surge pulse voltages, up to 6000 volts. SentryPlus™ auto shutdown and monitoring software is also included with SU-1000Li hardware.
SentryPlus™ Power Management and Diagnostic Software
- Plan a schedule to shutdown, restart, test UPS and control receptacles
- Customize programmable actions
- Set up notifications of user-defined power related events via pager, e-mail, audible alarm, network broadcast and SNMP trap
- View Real-time UPS data meters (voltage, frequency, loading percentage)
- Analyze power history and event records via software data and graphs
- Configure Multi-computer shutdown/wakeup through TCP/IP network
- Access remote monitoring, control and configuration through TCP/IP network
- Monitor and network multiple UPSs at a glance in a LAN
- Connect from either local or remote sites and Communicate to UPS using RS-232 or Universal Serial Bus (USB)
|